'''<u><span style="font-size:larger;">Basic Ebtron Info</span></u>'''
'''<u><span style="font-size:larger;">Basic Ebtron Info</span></u>'''


Ebtron airflow monitoring stations (AFMS) are typically mounted on the OA intake damper when specified for the job.&nbsp; They can also be used to measure CFM on any damper type, coil face area,&nbsp;blower inlet, etc.&nbsp; The GTA116-PC model is the standard for S-4.&nbsp; An AFMS&nbsp;uses a series of probes and sensors to measure the airflow through the damper.&nbsp; <span style="color:#e74c3c;">''(ADD MORE TECHNICAL INFO HERE -&nbsp;TDM;&nbsp;1/22/20)''</span>.
Ebtron airflow monitoring stations (AFMS) are typically mounted on the OA intake damper when specified for the job.&nbsp; They can also be used to measure CFM on any damper type, coil face area,&nbsp;blower inlet, etc.&nbsp; The GTA116-PC model is the standard for S-4, and our standard part numbers starts with 4091530<u>xxx</u>.&nbsp; An AFMS&nbsp;uses a series of probes and sensors to measure the airflow through the damper.&nbsp; <span style="color:#e74c3c;">''(ADD MORE TECHNICAL INFO HERE -&nbsp;TDM;&nbsp;1/22/20)''</span>.


&nbsp;
&nbsp;
Line 29: Line 29:
It is possible to use a single AFMS for multiple OA intake dampers (e.g. OA intake dampers on each side of the unit).&nbsp; If this is the case, Ebtron must be notified that the AFMS will be used on more than one damper, so they can determine the correct number of probes and sensors.
It is possible to use a single AFMS for multiple OA intake dampers (e.g. OA intake dampers on each side of the unit).&nbsp; If this is the case, Ebtron must be notified that the AFMS will be used on more than one damper, so they can determine the correct number of probes and sensors.


Also, make certain the&nbsp;requested cable length is adequate to run from the probes to the location of the AFMS controller.&nbsp; If the unit's control panel is a relatively far distance away from the AFMS probes, a&nbsp;separate panel is installed for the AFMS controller.
Also, make certain the&nbsp;requested cable length is adequate to run from the probes to the location of the AFMS controller.&nbsp; A 25' cable is our standard length, but 50' is available if needed.&nbsp; If the unit's control panel is a relatively far distance away from the AFMS probes, a&nbsp;separate panel is installed for the AFMS controller.


&nbsp;
&nbsp;

----


<span style="font-size:larger;"><u>'''Example Email #1'''</u></span>
<span style="font-size:larger;"><u>'''Example Email #1'''</u></span>
Line 100: Line 102:
&nbsp;
&nbsp;


----
<span style="font-size:larger;"><u>'''Email Example #2 - One (1) AFMS for Two (2) OA Dampers'''</u></span>

<span style="font-size:larger;"><u>'''Example Email&nbsp;#2 - One (1) AFMS for Two (2) OA Dampers'''</u></span>


'''<span style="font-size:10.0pt"><span style="font-family:">From:</span></span>'''<span style="font-size:10.0pt"><span style="font-family:">Tim Morris<br/> '''Sent:''' Thursday, September 11, 2014 11:16 AM<br/> '''To:''' Robert Koon<br/> '''Subject:''' FO #B866 Ebtron Ordering Info</span></span>
'''<span style="font-size:10.0pt"><span style="font-family:">From:</span></span>'''<span style="font-size:10.0pt"><span style="font-family:">Tim Morris<br/> '''Sent:''' Thursday, September 11, 2014 11:16 AM<br/> '''To:''' Robert Koon<br/> '''Subject:''' FO #B866 Ebtron Ordering Info</span></span>
Line 129: Line 133:


&nbsp;
&nbsp;

----


<span style="font-size:larger;"><u>'''Example Email #3 - Multiple Locations in a Single&nbsp;Unit'''</u></span>
<span style="font-size:larger;"><u>'''Example Email #3 - Multiple Locations in a Single&nbsp;Unit'''</u></span>


'''<span style="font-size:10.0pt"><span style="font-family:">From:</span></span>'''<span style="font-size:10.0pt"><span style="font-family:">Tim Morris<br/> '''Sent:''' Wednesday, June 13, 2012 1:04 PM<br/> '''To:''' Rick Rothschild<br/> '''Subject:''' FO #B223 Ebtron Ordering Info<br/> '''Importance:''' High</span></span>
'''<span style="font-size:10.0pt"><span style="font-family:">From:</span></span>'''<span style="font-size:10.0pt"><span style="font-family:">Tim Morris<br/> '''Sent:''' Wednesday, June 13, 2012 1:04 PM<br/> '''To:''' Rick Rothschild<br/> '''Subject:''' FO #B223 Ebtron Ordering Info</span></span>


&nbsp;
&nbsp;

Latest revision as of 21:46, 22 January 2020

Return to Engineering Main Menu

Basic Ebtron Info

Ebtron airflow monitoring stations (AFMS) are typically mounted on the OA intake damper when specified for the job.  They can also be used to measure CFM on any damper type, coil face area, blower inlet, etc.  The GTA116-PC model is the standard for S-4, and our standard part numbers starts with 4091530xxx.  An AFMS uses a series of probes and sensors to measure the airflow through the damper.  (ADD MORE TECHNICAL INFO HERE - TDM; 1/22/20).

 

Ordering Info

When ordering an Ebtron AFMS, you must send the design info to Purchasing, so they can add details to the P.O. and relay the info to Ebtron.  When ordering, you must include:

 

  • Damper Size (width x height).
    • Note: This is total damper size if more than one damper are used for a single AFMS.
    • E.G. 48" x 60" total size for two (2) individual 24" x 60" dampers.
  • Mounting Type (e.g. Stand-off mounting).
  • Cable Length (e.g. 25')
  • Maximum Airflow (CFM) thru Damper.
  • Face Velocity (FPM) thru Damper @ Max CFM.
  • Drawing showing the location of the AFMS in the unit.
  • Job Location (i.e. city, state).
  • Seasons-4 Part Number(s)

 

When ordering the AFMS, it is preferred that Ebtron determines the required number of probes and sensors.  Our part number descriptions will not show this info for all future new P/N setups.  Any existing P/N that has the correct damper size for your application can be used, but it is recommended that any detail describing the number or probes, sensors and cable length be removed from the existing P/N descriptions.  Ask Purchasing to make this change before issuing the P.O.

It is possible to use a single AFMS for multiple OA intake dampers (e.g. OA intake dampers on each side of the unit).  If this is the case, Ebtron must be notified that the AFMS will be used on more than one damper, so they can determine the correct number of probes and sensors.

Also, make certain the requested cable length is adequate to run from the probes to the location of the AFMS controller.  A 25' cable is our standard length, but 50' is available if needed.  If the unit's control panel is a relatively far distance away from the AFMS probes, a separate panel is installed for the AFMS controller.

 


Example Email #1

From:Gary Moncus
Sent: Thursday, January 02, 2020 2:19 PM
To: Robert Koon
Subject: D415 CORLISS HIGH SCHOOL - Ebtron Order

 

Robert,

For FO #D415, we are ordering three Ebtron airflow station. I have listed the S4 part numbers, airflows, damper sizes, and velocities on the table below.

Unit Tag

OA Damper (WxH inches)

Face Velocity (fpm)

CFM

Part #

First Description

Second Description

S-20

30”X60”

1431

17,889

4091530235

GTA116-PC FLOW STATION

(30X60) DAMPER

S-22

30”X72”

1552

23,283

4091530210

GTA116-PC FLOW STATION

(30X72) DAMPER

S-23

30”X60”

1042

13,031

4091530235

GTA116-PC FLOW STATION

(30X60) DAMPER

             

 

Each airflow station will measure ONE outdoor air intake dampers. The OA intake damper sizes are listed on the table above for each unit.

FYI: we may have ordered these part numbers in the past, but the design and orientations may be different than the requirements for this job.

Please have Ebtron design the GTA116 system with the appropriate number of probes and sensors for each unit. The probes will have stand-off mounting. We need 25’ cable length. Attached are the unit drawings showing the locations of the dampers and the station locations are still being finalized but will be within 25’. If more information is required, please let me know. Thanks for the help.

 

Gary

 


Example Email #2 - One (1) AFMS for Two (2) OA Dampers

From:Tim Morris
Sent: Thursday, September 11, 2014 11:16 AM
To: Robert Koon
Subject: FO #B866 Ebtron Ordering Info

 

Robert,

For FO #B866, we are ordering one (1) Ebtron airflow station for each unit for a total of two (2) airflow stations. The following part is required for each unit (RTU-1 & RTU-2):

 

4091530196 (Qty 1 per unit) - GTA116-PC FLOW STATION (36X96)

 

For each unit, the single airflow station will measure the airflow of two (2) outdoor air intake dampers. Each damper is 18” x 96”. Please have Ebtron design the GTA116 system with the appropriate number of probes and sensors. The probes will have stand-off mounting. We need 25’ wire length. Attached are the unit drawings in case Ebtron needs them.

 

Please add all of this information to the PO, so Ebtron knows what is required. FYI: we have ordered this part number in the past, but the design and orientation was different than the requirements for this job. If more information is required, please let me know.

 

Thanks,

Tim

 


Example Email #3 - Multiple Locations in a Single Unit

From:Tim Morris
Sent: Wednesday, June 13, 2012 1:04 PM
To: Rick Rothschild
Subject: FO #B223 Ebtron Ordering Info

 

Rick,

For FO #B223, we are ordering three (3) Ebtron airflow stations. This job is very similar to FO #A829. I will include as much information as I can in this email, so you can forward it on to Bill Jones at Ebtron. Bill can review the attached email from the previous job for reference. The following parts are required for each unit:

 

P/N 4091530167 (Qty 2) - GTA116-PC FLOW STATION (30x30)

P/N 4091530190 (Qty 1) - GTA116-PC FLOW STATION (12x12)

 

Here is a description of each required airflow station:

  1. P/N 4091530167 (Qty 1)
    1. Measures a 30” x 30” OA damper
    2. Standoff Mounting
    3. 25’ Wire Length

 

  1. P/N 4091530167 (Qty 1)
    1. Measures a 30” x 30” SC coil face area
    2. Standoff Mounting
    3. 25’ Wire Length

 

  1. P/N 4091530190 (Qty 1)
    1. Measures a 12” x 12” minimum EA damper.
    2. Insertion Mounting
    3. 25’ Wire Length

 

Please have Ebtron design the GTA116 systems with the appropriate number of probes and sensors. Attached is the unit drawing. It shows the locations of the airflow monitoring stations. All probes mount upstream of the measured opening (i.e. damper or coil). If more information is required, please let me know. Thanks for the help.

 

Thanks,

Tim